1、1#樓計算負荷及配電干線表,序號,供電區域名稱,裝設功率(kW),需要系數(KX),計算功率Pjs(kW),無功功率Qjs(kvar),視在功率Sjs(kVA),功率因數COS,tan,整定電流(A),計算電流(A),干線線徑,配電箱編號,備注1,區排煙、加壓送風,83.90 ,1.00 ,0.80 ,0.75,200,159.30 ,2(ZR-EE-4*120+70),雙電源切換(消防電源)2,、區排煙、加壓送風,62.20 ,1.00 ,0.80 ,0.75,200,118.10 ,2(ZR-EE-4*120+7),雙電源切換(消防電源)3,消防值班室,12.90 ,1.00 ,12.90

2、 ,12.13 ,0.73 ,0.94,63,38.10 ,2(ZR-EE-4*+),雙電源切換4,消防水泵放,71.10 ,1.00 ,0.80 ,0.75,200,137.60 ,2(ZR-EE-4*120+70),雙電源切換(消防電源)5,(區)消防電梯,40.00 ,0.20 ,8.00 ,6.00 ,0.80 ,0.75,100,2(ZR-EE-4*+),雙電源切換6,區電梯,40.00 ,0.20 ,8.00 ,6.00 ,0.80 ,0.75,100,2(ZR-EE-4*+),雙電源切換7,區電梯,24.80 ,0.20 ,4.96 ,3.72 ,0.80 ,0.75,63,2(

3、ZR-EE-4*+),雙電源切換8,區電梯,20.00 ,0.20 ,4.00 ,3.00 ,0.80 ,0.75,63,2(ZR-EE-4*+),雙電源切換9,人防設備,20.00 ,0.80 ,0.75,63,2(ZR-EE-4*+),雙電源切換(消防電源)10,網絡機房設備、照明,129.20 ,0.81 ,104.65 ,100.46 ,0.72 ,0.96,315,226.00 ,2(ZR-EE-4*+),雙電源切換11,網絡機房空調、鍋爐房應急排風,201.60 ,0.71 ,143.14 ,107.36 ,0.80 ,0.75,350,271.80 ,(ZR-EE-4*120+7

4、0),個回路、每個回路根線(雙電源切換)12,間、分配線間,26.60 ,1.00 ,26.20 ,25.15 ,0.72 ,0.96,80,58.20 ,2(ZR-EE-4*+),雙電源切換13,冷水機組,214.00 ,1.00 ,214.00 ,132.68 ,0.85 ,0.62,500,382.50 ,2(ZR-EE-4*1+),14,冷水機組,214.00 ,1.00 ,0.85 ,0.62,500,382.50 ,2(ZR-EE-4*1+),備用15,設備房、鍋爐房,255.60 ,0.98 ,250.49 ,180.35 ,0.81 ,0.72,630,475.30 ,2(ZR

5、-EE-4*+),非雙電源16,生活水泵房,33.80 ,0.95 ,32.11 ,24.08 ,0.80 ,0.75,80,61.20 ,ZR-EE-4*+,兩用一備17,地下一層插座、照明,33.20 ,0.60 ,19.92 ,15.54 ,0.79 ,0.78,63,42.70 ,ZR-EE-4*+,+,18,區照明,114.70 ,0.90 ,103.23 ,49.55 ,0.90 ,0.48,315,204.30 ,ZR-EE-4*+,19,區插座,282.20 ,0.70 ,197.54 ,201.49 ,0.70 ,1.02,630,430.80 ,2(ZR-EE-4*+),2

6、0,區新風機組、風機盤管,63.90 ,1.00 ,63.90 ,47.93 ,0.80 ,0.75,200,126.30 ,ZR-EE-4*120+70,21,區照明,74.20 ,0.90 ,66.78 ,32.05 ,0.90 ,0.48,200,140.50 ,ZR-EE-4*120+70,22,區插座,165.50 ,0.77 ,127.44 ,129.99 ,0.70 ,1.02,350,278.10 ,2(ZR-EE-4*120+70),23,區新風機組、風機盤管,36.60 ,1.00 ,36.60 ,27.45 ,0.80 ,0.75,125,70.80 ,ZR-EE-4*+

7、,24,區一層照明、插座、新風機組、風機盤管,39.30 ,0.88 ,34.58 ,24.90 ,0.81 ,0.72,100,74.00 ,ZR-EE-4*+,25,區二層照明、插座、新風機組、風機盤管,36.80 ,0.87 ,32.02 ,22.41 ,0.82 ,0.70 ,100,67.20 ,ZR-EE-4*+,26,區三五層照明、插座、新風機組、風機盤管,76.40 ,0.87 ,66.47 ,47.86 ,0.81 ,0.72,200,140.90 ,ZR-EE-4*120+70,合計,2372.50 ,1556.93 ,1200.10 ,取KP=KQ=0.90,1401.24,1080.09,1769.2,自然功率因數:COS1=1401.24/1769.20=0.79,tan1=0.78,經無功補償后功率因數COS2=0.90,tan2=

溫馨提示

  • 1. 本站所有資源如無特殊說明,都需要本地電腦安裝OFFICE2007和PDF閱讀器。圖紙軟件為CAD,CAXA,PROE,UG,SolidWorks等.壓縮文件請下載最新的WinRAR軟件解壓。
  • 2. 本站的文檔不包含任何第三方提供的附件圖紙等,如果需要附件,請聯系上傳者。文件的所有權益歸上傳用戶所有。
  • 3. 本站RAR壓縮包中若帶圖紙,網頁內容里面會有圖紙預覽,若沒有圖紙預覽就沒有圖紙。
  • 4. 未經權益所有人同意不得將文件中的內容挪作商業或盈利用途。
  • 5. 人人文庫網僅提供信息存儲空間,僅對用戶上傳內容的表現方式做保護處理,對用戶上傳分享的文檔內容本身不做任何修改或編輯,并不能對任何下載內容負責。
  • 6. 下載文件中如有侵權或不適當內容,請與我們聯系,我們立即糾正。
  • 7. 本站不保證下載資源的準確性、安全性和完整性, 同時也不承擔用戶因使用這些下載資源對自己和他人造成任何形式的傷害或損失。

評論

0/150

提交評論