數據中心設計規范CodeforDesignofDataCenters目次1總則··························································································(1)2術語··························································································(2)3分級與性能要求······································································(7)3.1分級·················································································(7)3.2性能要求·········································································(7)4選址及設備布置······································································(9)4.1選址·················································································(9)4.2組成·················································································(9)4.3設備布置·········································································(10)5環境要求····················································································(11)5.1溫度、露點溫度及空氣粒子濃度·································(11)5.2噪聲、電磁干擾、振動及靜電·······································(11)6建筑與結構··············································································(12)6.1一般規定·········································································(12)6.2人流、物流及出入口······················································(12)6.3圍護結構熱工設計和節能措施········································(13)6.4室內裝修··········································································(13)7空氣調節·····················································································(15)7.1一般規定··········································································(15)7.2負荷計算··········································································(15)7.3氣流組織··········································································(15)7.4系統設計··········································································(16)7.5設備選擇··········································································(17)8電氣····························································································(19)8.1供配電·················································································(19)8.2照明···················································································(21)8.3靜電防護···········································································(21)8.4防雷與接地·······································································(22)9電磁屏蔽······················································································(24)9.1一般規定···········································································(24)9.2結構形式···········································································(24)9.3屏蔽件·················································································(24)10網絡與布線系統·········································································(26)10.1網絡系統··········································································(26)10.2布線系統··········································································(26)11智能化系統···················································································(28)11.1一般規定··········································································(28)11.2環境和設備監控系統······················································(28)11.3安全防范系統····································································(29)11.4總控中心············································································(29)12給水排水···················································································(30)12.1一般規定··········································································(30)12.2管道敷設··········································································(30)13消防與安全···············································································(31)13.1一般規定··········································································(31)13.2防火與疏散········································································(31)13.3消防設施········································································(33)13.4安全措施········································································(33)附錄A各級數據中心技術要求························································(34)本規范用詞說明············································································(41)引用標準名錄··················································································(42)附:條文說明··················································································(43)Contents1Generalprovisions·······························································(1)2Terms·····························································································(2)3Ratingclassificationandrequiredfeatures······(7)3.1Ratingclassification·············································(7)3.2Requiredfeatures······················································(7)4Siteselectionandequipmentlayout···························(9)4.1Siteselection······························································(9)4.2Composition·····································································(9)4.3Equipmentlayout·························································(10)5Environmentalrequirement·················································(11)5.1Temperature,dewpointtemperatureandairborneparticleconcentration·····································································(11)5.2Noise,electromagneticinterference,vibrationandstaticelectricity··············································································(11)6Buildingandstructure························································(12)6.1General·············································································(12)6.2Peopleflowandgoodsflow,entrancesandexits············································································································(12)6.3Retainingstructurethermaldesignandenergysavingmeasure········································································································(13)6.4Interiordesign·····························································(13)7Airconditioning········································································(15)7.1General···············································································(15)7.2Thermalloadcalculation····································(15)7.3Airflowmanagement··················································(15)7.4Systemdesign·····························································(16)7.5Equipmentselection················································(17)8ElectricalSystems·······························································(19)8.1PowerSupplyanddistribution···························(19)8.2Lighting···········································································(21)8.3Electrostaticdischargeprotection················(21)8.4Lightningprotectionandgrounding················(22)9ElectromagneticShielding·················································(24)9.1General·············································································(24)9.2Shieldingstructure··················································(24)9.3Shieldingobjects······················································(24)10Networkandcablingsystem·············································(26)10.1Networksystem····························································(26)10.2Cablingsystem····························································(26)11Intelligentsystem·······························································(28)11.1General············································································(28)11.2Environmentandequipmentmonitoring·········(28)11.3Securitysystem··························································(29)11.4Enterprisecommandcenter····································(29)12Watersupplyanddrainage······················································(30)12.1General·················································································(30)12.2Pipinglayout·····································································(30)13Fireprotectionandsafety······················································(31)13.1General·············································································(31)13.2Firepreventionandevacuation·························(31)13.3Fireprotectionfacilities··································(33)13.4Safetymeasure·····························································(33)AppendixA:TechnicalRequirementsforCenterRatingsDefinitionofkeywords····························································(34)Explanationofwordinginthiscode··········································(41)Listofquotedstandards·································································(42)Addition:Explanationofprovisions········································(43)1總則1.0.1為規范數據中心的設計,確保電子信息系統安全、穩定、可靠地運行,做到技術先進、經濟合理、安全適用、節能環保,制定本規范。1.0.2本規范適用于新建、改建和擴建的數據中心的設計。1.0.3數據中心的設計應遵循近期建設規模與遠期發展規劃協調一致的原則。1.0.4數據中心的設計除應符合本規范外,尚應符合國家現行有關標準的規定。12術語2.0.1數據中心datacenter也可以是一棟建筑物的一部分,包括主機房、輔助區、支持區和行政管理區等。2.0.2災備數據中心recoverycenter用于災難發生時,接替生產系統運行,進行數據處理和支持關鍵業務功能繼續運作的場所,包括限制區、普通區和專用區。2.0.3room主要用于數據處理設備安裝和運行的建筑空間,包括服務器機房、網絡機房、存儲機房等功能區域。2.0.4auxiliary用于電子信息設備和軟件的安裝、調試、維護、運行監控和管理的場所,包括進等區域。2.0.5supportarea為主機房、輔助區提供動力支持和安全保障的區域,包括變配電室、柴油發電機房、電池室、空調機房、動力站房、不間斷電源系統用房、消防設施用房等。2.0.6administrativearea用于日常行政管理及客戶對托管設備進行管理的場所,包括辦公室、門廳、值班室、盥洗室、更衣間和用戶工作室等。2.0.7restricted2.0.8regulararea用于災難恢復和日常訓練、辦公的場所。2.0.9基礎設施infrastructure數據中心內,為電子信息設備提供運行保障的設施。2.0.10電子信息設備electronicinformationequipment2對電子信息進行采集、加工、運算、存儲、傳輸、檢索等處理的設備,包括服務器、交換機、存儲設備等。2.0.11冗余redundancy重復配置系統的一些或全部部件,當系統發生故障時,冗余配置的部件介入并承擔故障部件的工作,由此延長系統的平均故障間隔時間。2.0.12——基本需求N——requirement系統滿足基本需求,沒有冗余。2.0.13冗余N+Xredundancy個組件、X個單元、X個模塊或XX個組件、單元、模塊或路徑的故障或維護不會導致系統運行中斷。(~N)2.0.14容錯faulttolerant子信息設備正常運行的基本需求。2.0.15電磁干擾()electromagneticinterference電磁騷擾引起的裝置、設備或系統性能的下降。2.0.16電磁屏蔽electromagneticshielding用導電材料減少交變電磁場向指定區域的穿透。2.0.17電磁屏蔽室electromagneticshieldingenclosure專門用于衰減、隔離來自內部或外部電場、磁場能量的建筑空間體。2.0.18截止波導通風窗cut-offwaveguidevent范圍內的電磁波。2.0.19可拆卸式電磁屏蔽室modularelectromagneticshieldingenclosure現場裝配,組建成具有可拆卸結構的電磁屏蔽室。2.0.20焊接式電磁屏蔽室weldedelectromagneticshieldingenclosure3主體結構采用現場焊接方式建造的具有固定結構的電磁屏蔽室。2.0.21配電列頭柜(RPP)remotepowerpanel為成行排列或按功能區劃分的機柜提供配電管理的設備。2.0.22網絡配線柜horizontaldistributioncabinet為成行排列或按功能區劃分的機柜提供網絡服務的水平配線區設備。2.0.23智能布線管理系統intelligentcablingmanagementsystem布線系統和網絡設備連接的智能化管理,跟蹤、記錄和報告。2.0.24靜態staticstate要求,但電子信息設備未運行。2.0.25動態dynamicstate主機房的空調系統和電子信息設備處于正常運行狀態,室內有相關人員在場的情況。2.0.26停機條件stopcondition備的停機要求,電子信息設備處于停機狀態。2.0.27靜電泄放electrostaticleakage帶電體上的靜電電荷通過帶電體內部或其表面等途徑,部分或全部消失的現象。2.0.28體積電阻volumeresistance在材料相對的兩個表面上放置的兩個電極間所加直流電壓與流過兩個電極間的穩態電流(不包括沿材料表面的電流)2.0.29保護性接地protectiveearthing以保護人身和設備安全為目的的接地。2.0.30功能性接地functionalearthing用于保證設備(系統)正常運行,正確地實現設備(系統)功能的接地。2.0.31接地線earthingconductor從接地端子或接地匯集排至接地極的連接導體。2.0.32等電位聯結帶bondingbar4其上形成等電位聯結的金屬帶。2.0.33等電位聯結導體bondingconductor將分開的諸導電性物體連接到接地匯集排、等電位聯結帶或等電位聯結網格的導體。2.0.34電能利用效率(PUE)powerusageeffectiveness與所有電子信息設備消耗的總電能之比。2.0.35水利用效率()waterusageeffectiveness所有電子信息設備消耗的總電能之比。2.0.36自動轉換開關電器(ATSE)automatictransferswitchingequipment幾個負載電路從一個電源自動轉換至另一個電源的電器。2.0.37計算流體動力學(CFD)computationalfluiddynamics度場、壓力場、速度場等計算方法。2.0.38雙重電源duplicatesupply的。2.0.39總控中心()enterprisecommandcenter監控中心。2.0.40不間斷電源系統()uninterruptiblepowersystem直流電源,在一定時間內,維持對負載供電的連續性。2.0.41總體擁有成本(TCO)Totalcostofownership數據中心全生命周期內,建設費用和運行費用的總和。2.0.42云計算cloudcomputing5供的可配置運算資源,該資源可以快速部署與發布。2.0.43DCIM)CenterInfrastructureManagement并優化數據中心的性能。63分級與性能要求3.1分級3.1.1數據中心應劃分為A、、C三級。設計時應根據數據中心的使用性質、數據丟失或網絡中斷在經濟或社會上造成的損失或影響程度確定所屬級別。3.1.2符合下列情況之一的數據中心應為級:1電子信息系統運行中斷將造成重大的經濟損失;2電子信息系統運行中斷將造成公共場所秩序嚴重混亂。3.1.3符合下列情況之一的數據中心應為級。1電子信息系統運行中斷將造成較大的經濟損失;2電子信息系統運行中斷將造成公共場所秩序混亂。3.1.4不屬于級或B級的數據中心應為C3.1.5在同城或異地建立的災備數據中心,設計時宜與主用數據中心等級相同。3.1.6等級按照其中最低等級部分確定。3.2性能要求3.2.1級數據中心的基礎設施宜按容錯系統配置,在電子信息系統運行期間,基礎設施應在一次意外事故后或單系統設備維護或檢修時仍能保證電子信息系統正常運行。3.2.2級數據中心同時滿足下列要求時,電子信息設備的供電可采用不間斷電源系統和市電電源系統相結合的供電方式。1設備或線路維護時,應保證電子信息設備正常運行;2市電直接供電的電源質量應滿足電子信息設備正常運行的要求;3市電接入處的功率因數應符合當地供電部門的要求;4柴油發電機系統應能夠承受容性負載的影響;5向公用電網注入的諧波電流分量(方均根值)不應超過現行國家標準《電能質量公用電網諧波》GB/T14549規定的諧波電流允許值。73.2.3系統配置。3.2.4級數據中心的基礎設施應按冗余要求配置,在電子信息系統運行期間,基礎設施在冗余能力范圍內,不應因設備故障而導致電子信息系統運行中斷。3.2.5級數據中心的基礎設施應按基本需求配置,在基礎設施正常運行情況下,應保證電子信息系統運行不中斷。84選址及設備布置4.1選址4.1.1數據中心選址應符合下列要求:1電力供給應充足可靠,通信應快速暢通,交通應便捷;2采用水蒸發冷卻方式制冷的數據中心,水源應充足。3自然環境應清潔,環境溫度應有利于節約能源;4應遠離產生粉塵、油煙、有害氣體以及生產或貯存具有腐蝕性、易燃、易爆物品的場所;5應遠離水災、地震等自然災害隱患區域;6應遠離強振源和強噪聲源;7應避開強電磁場干擾;8A級數據中心不宜建在公共停車庫的正上方;9大中型數據中心不宜建在住宅小區和商業區內。4.1.2題進行綜合分析和經濟比較。4.2組成4.2.1區、支持區、行政管理區等功能區組成。4.2.2應預留今后業務發展需要的使用面積。主機房的使用面積可按下式確定:A=SN(4.2.2)式中A主機房的使用面積(㎡);S——2.0~4.0(㎡臺);N——主機房內所有機柜(架)、大型電子信息設備和列頭柜等設備的總臺數。94.2.3輔助區和支持區的面積之和可為主機房面積的倍~倍。4.2.4用戶工作室的使用面積可按㎡/5㎡/人長期工作的房間,使用面積可按㎡/7㎡/4.2.5在災難發生時,仍需保證電子信息業務連續性的單位,應建立災備數據中心。專用區。4.3設備布置4.3.1人員操作和安全、設備和物料運輸、設備散熱、安裝和維護的要求。4.3.2容錯系統中相互備用的設備應布置在不同的物理隔間內,相互備用的管線宜沿不同路徑敷設。4.3.3/后出風冷卻方式,且機柜自身結構未采用封閉冷風通道或封閉熱風通道方式時,機柜(架)的布置宜采用面對面、背對背方式。4.3.4主機房內通道與設備間的距離應符合下列規定:1用于搬運設備的通道凈寬不應小于1.5m;2面對面布置的機柜(架)正面之間的距離不宜小于1.2m;3背對背布置的機柜(架)背面之間的距離不宜小于0.8m;4當需要在機柜(架)側面和后面維修測試時,機柜(架)與機柜(架)、機柜(架)與墻之間的距離不宜小于1.0m;5成行排列的機柜(架),其長度超過6m時,兩端應設有通道;當兩個通道之間的距離超過時,在兩個通道之間還應增加通道。通道的寬度不宜小于1m可為0.8m。105環境要求5.1溫度、露點溫度及空氣粒子濃度5.1.1求;當電子信息設備尚未確定時,應按照附錄A的要求執行。5.1.2或等于μm的懸浮粒子數應少于17,600,000粒。5.1.3數據中心裝修后的室內空氣質量除應符合本規范的規定外,尚應符合現行國家標準《室內空氣質量標準》GB/T18883的有關規定。5.2噪聲、電磁干擾、振動及靜電5.2.1總控中心內,在長期固定工作位置測量的噪聲值應小于60dB(A5.2.2主機房和輔助區內的無線電騷擾環境場強在~1000MHz和1400MHz~2000MHz頻段范圍內不應大于(μ);工頻磁場場強不應大于30A/m。5.2.3大于500mm/s2。5.2.4主機房和輔助區內絕緣體的靜電電壓絕對值不應大于。116建筑與結構6.1一般規定6.1.1建筑和結構設計應根據數據中心的等級,按本規范附錄的要求執行。6.1.2建筑平面和空間布局應具有靈活性,并應滿足數據中心的工藝要求。6.1.3機房凈高不宜小于3.0m。6.1.4變形縫不宜穿過主機房。6.1.5鄰。6.1.6和維護要求。當管線需穿越樓層時,宜設置技術豎井。6.1.7A級數據中心的抗震設防類別不應低于乙類,B級和C級數據中心的抗震設防類別不應低于丙類。6.1.8改建的數據中心應根據荷載要求,按照《建筑抗震鑒定標準》的規定加固結構規范》GB50367、《建筑抗震加固技術規程》116和《混凝土結構后錨固技術規程》JGJ145的規定進行加固。當抗震設防類別為丙類的建筑改建為A級數據中心時,在使用荷載滿足要求的條件下,建筑可不做加固處理。6.1.9新建A級數據中心首層建筑完成面應高出當地洪水百年重現期水位線1.0m以上,并應高出室外地坪最少0.6m。6.2人流、物流及出入口6.2.1數據中心宜單獨設置人員出入口和貨物出入口。6.2.2有人操作區域和無人操作區域宜分開布置。6.2.3主機房的通道凈寬不應小于1.5m。6.2.4人數的1m2/3m2/人計算。126.3圍護結構熱工設計和節能措施6.3.1GB50189構的熱工性能應根據全年動態能耗分析情況確定最優值。6.3.2外墻、屋面熱橋部位的內表面溫度不應低于室內空氣露點溫度。6.3.3門窗氣密、水密、抗風壓性能分級及檢測方法》GB/T7106規定的級要求或采用雙層GB50189確定。不間斷電源系統的電池室設有外窗時,應避免陽光直射。6.4室內裝修6.4.1家標準《建筑內部裝修設計防火規范》GB50222的有關規定。6.4.2未經表面改性處理的高分子絕緣材料作為面層。6.4.3避免眩光,并應減少凹凸面。6.4.4高度應根據電纜布線和空調送風要求確定,并應符合下列規定:1活動地板下的空間只作為電纜布線使用時,地板高度不宜小于250mm。活動地板下的地面和四壁裝飾,可采用水泥砂漿抹灰。地面材料應平整、耐磨;2500mm。面應采取保溫、防潮措施,一層地面墊層宜配筋,圍護結構宜采取防結露措施。6.4.5宜設置檢修通道或檢修口。136.4.6當主機房內設有用水設備時,應采取防止水漫溢和滲漏措施。6.4.7門窗、墻壁、地(樓)面的構造和施工縫隙,均應采取密閉措施。6.4.8保護。147空氣調節7.1一般規定7.1.1數據中心的空氣調節系統設計應根據數據中心的等級,按本規范附錄的要求調節設計規范》GB50736的有關規定。7.1.2與其它功能用房共建于同一建筑內的數據中心,宜設置獨立的空調系統。7.1.3主機房與其它房間宜分別設置空調系統。7.2負荷計算7.2.1電子信息設備和其它設備的散熱量應根據設備實際用電量進行計算。7.2.2空調系統夏季冷負荷應包括下列內容:1數據中心內設備的散熱;2建筑圍護結構得熱;3通過外窗進入的太陽輻射熱;4人體散熱;5照明裝置散熱;6新風負荷;7伴隨各種散濕過程產生的潛熱。7.2.3空調系統濕負荷應包括下列內容:1人體散濕;2新風濕負荷;3滲漏空氣濕負荷;4圍護結構散濕。7.3氣流組織7.3.115要求時,主機房氣流組織形式、風口及送回風溫差可按表7.3.1選用。表7.3.1主機房氣流組織形式、風口及送回風溫差氣流組織形式下送上回上送上回(或側回)側送側回1.1.活動地板風口(可帶調節閥)2.1.百葉風口送風口2.帶可調多葉閥的格柵風口3.百葉風口2.格柵風口3.其它風口4.格柵風口3.其它風口5.其它風口回風口1、格柵風口、百葉風口、網板風口4、其它風口送回風溫差8℃~℃送風溫度應高于室內空氣露點溫度7.3.2對單臺機柜發熱量大于4kW/冷空調前送風后回風等方式,并宜采取冷熱通道隔離措施。7.3.3在有人操作的機房內,送風氣流不宜直對工作人員。7.4系統設計7.4.1采用冷凍水空調系統的A級數據中心宜設置蓄冷設施,蓄冷時間應滿足電子信心運行需要時,A級數據中心也可采用兩種冷源供應方式。7.4.2B1級材料。冷表面應作隔氣、保溫處理。7.4.3采用活動地板下送風時,地板的高度應根據送風量確定。7.4.4主機房應維持正壓。主機房與其它房間、走廊的壓差不宜小于5Pa,與室外靜壓差不宜小于10Pa。7.4.5空調系統的新風量應取下列二項中的最大值:1按工作人員計算,每人3;2維持室內正壓所需風量。167.4.6末級過濾裝置宜設置在正壓端。7.4.77.4.8物隨氣流進入其它房間的措施。7.4.9房內。7.4.10空調系統設計應采用下列節能措施:1空調系統應根據當地氣候條件,充分利用自然冷源。2的空調系統,設計時應采用自然冷卻技術。3空調系統可采用電制冷與自然冷卻相結合的方式。4用經濟效益最大的節能設計方案。5空氣質量優良地區,可采用全新風空調系統。6根據負荷變化情況,空調系統宜采用變頻、自動控制等技術進行負荷調節。7.4.11凍措施。7.5設備選擇7.5.1空調和制冷設備的選用應符合運行可靠、經濟適用、節能和環保的要求。7.5.2等進行選擇,并應按本規范附錄A的要求執行。7.5.3~的余量。7.5.4機房專用空調、行間制冷空調宜采用出風溫度控制。空調機應帶有通信接口,17也可由其他加濕器進行調節。7.5.5維修空間。188電氣8.1供配電8.1.1數據中心用電負荷等級及供電要求應根據數據中心的等級,按現行國家標準《供配電系統設計規范》GB50052及本規范附錄A的要求執行。8.1.2電子信息設備供電電源質量應根據數據中心的等級,按本規范附錄A的要求執行。當電子信息設備采用直流電源供電時,供電電壓應符合電子信息設備的要求。8.1.3供配電系統應為電子信息系統的可擴展性預留備用容量。8.1.4戶外供電線路不宜采用架空方式敷設。8.1.5壓器宜靠近負荷布置。8.1.6數據中心低壓配電系統的接地型式宜采用備,其配電系統應采用TN-S8.1.7按下式計算:E≥1.2P(8.1.7-1)式中E不間斷電源系統的基本容量(不包含備份不間斷電源系統設備(kW/kVAP——電子信息設備的計算負荷(kW/kVA8.1.8數據中心內采用不間斷電源系統供電的空調設備和電子信息設備不應由同一采用不同的不間斷電源系統。8.1.9電子信息設備的配電宜采用配電列頭柜或專用配電母線。采用配電列頭柜時,8.1.10交流配電列頭柜和交流專用配電母線宜配備瞬態電壓浪涌保護器和電源監測PE線之間的電位差不能滿足電子信息設備使用要求時,配電系統可裝設隔離變壓器。198.1.11電子信息設備的電源連接點應與其他設備的電源連接點嚴格區別,并應有明顯標識。8.1.12級數據中心應由雙重電源供電,并應設置備用電源。備用電源宜采用獨立于正常電源發生故障時,備用電源應能承擔數據中心正常運行所需要的用電負荷。8.1.13級數據中心宜由雙重電源供電,當只有一路電源時,應設置柴油發電機組作為備用電源。8.1.14后備柴油發電機組的性能等級不應低于級;級數據中心發電機組應連續和不限時運行,發電機組的輸出功率應滿足數據中心最大平均負荷的需要。B級數據中心發電機組的輸出功率可按限時500h運行功率選擇。8.1.15柴油發電機應設置現場儲油裝置,儲存柴油的供應時間應按本規范附錄A的要進行更換和補充。8.1.16柴油發電機周圍應設置檢修用照明和維修電源,電源宜由不間斷電源系統供電。8.1.17正常電源與備用電源之間的切換采用自動轉換開關電器時,自動轉換開關電電源的切換。8.1.18同城災備數據中心與主用數據中心的供電電源不應來自同一個城市變電站。采用分布式能源供電的數據中心,備用電源可采用市電或柴油發電機。8.1.19敷設在隱蔽通風空間的配電線路宜采用低煙無鹵阻燃銅芯電纜,也可采用配線槽(橋架)或配電母線的布置不應阻斷氣流通路。8.1.20配電線路的中性線截面積不應小于相線截面積;單相負荷應均勻地分配在三相線路上。208.2照明8.2.1主機房和輔助區一般照明的照度標準值應按照300lx~500lx設計,一般顯色指數不宜小于80。支持區和行政管理區的照度標準值應按現行國家標準《建筑照明設計標準》GB50034的有關規定執行。8.2.2主機房和輔助區內的主要照明光源宜采用高效節能熒光燈,也可采用燈。熒光燈鎮流器的諧波限值應符合現行國家標準《電磁兼容限值諧波電流發射限值》GB17625.1的有關規定,燈具應采取分區、分組的控制措施。8.2.3輔助區的視覺作業宜采取下列保護措施:1視覺作業不宜處在照明光源與眼睛形成的鏡面反射角上;2輔助區宜采用發光表面積大、亮度低、光擴散性能好的燈具;3視覺作業環境內宜采用低光澤的表面材料。8.2.4于0.7,非工作區域內的一般照明照度值不宜低于工作區域內一般照明照度值的1/3。8.2.5的10%50%明可為一般照明的一部分。8.2.6值不應低于5,其它區域通道疏散照明的照度值不應低于1。8.2.8數據中心內的照明線路宜穿鋼管暗敷或在吊頂內穿鋼管明敷。8.2.9電。8.3靜電防護8.3.1工程防靜電設計規范》GB50611的有關規定。8.3.2×~1.0109Ω具有防火、環保、耐污耐磨性能。218.3.3主機房和輔助區中不使用防靜電活動地板的房間可鋪設防靜電地面,其靜電耗散性能應長期穩定,且不應起塵。8.3.4規范第8.3.18.3.5采用導電膠與接地導體粘接時,其接觸面積不宜小于20cm2。8.4防雷與接地8.4.1并應符合現行國家標準《建筑物防雷設計規范》和《建筑物電子信息系統防雷技術規范》的有關規定。8.4.2定。8.4.3接地線絕緣;供電線路與接地線宜同路徑敷設。8.4.4等必須進行等電位聯結并接地。8.4.5電子信息設備等電位聯結方式應根據電子信息設備易受干擾的頻率及數據中心的等級和規模確定,可采用S型、型或混合型。8.4.6MSM混合型等電位聯結方式時,主機房應設置等電位聯結網格,網格柜)應采用兩根不同長度的等電位聯結導體就近與等電位聯結網格連接。8.4.7等電位聯結網格應采用截面積不小于25mm2的銅帶或裸銅線,并應在防靜電活動地板下構成邊長為沒~的矩形網格。8.4.88.4.8的要求。表8.4.8等電位聯結帶、接地線和等電位聯結導體的材料和最小截面積22名稱材料截面積(mm2)等電位聯結帶銅50利用建筑內的鋼筋做接地線鐵50單獨設置的接地線銅25等電位聯結導體(從等電位聯結帶至接地匯集排或至其它等電位銅16聯結帶;各接地匯集排之間)等電位聯結導體(從機房內各金屬裝置至等電位聯結帶或接地匯銅6集排;從機柜至等電位聯結網格)8.4.9~10kV備用柴油發電機系統中性點接地方式應根據常用電源接地方式及線用低電阻接地系統時,可采用其中一臺機組接地方式。8.4.10及以下備用柴油發電機系統中性點接地方式宜與低壓配電系統接地方式一性點可經電抗器接地,也可采用其中一臺機組接地方式。239電磁屏蔽9.1一般規定9.1.1或采取其它電磁泄漏防護措施,電磁屏蔽室的性能指標應按國家現行有關標準執行。9.1.2對于環境要求達不到本規范第5.2.29.1.3電磁屏蔽室的結構形式和相關的屏蔽件應根據電磁屏蔽室的性能指標和規模選擇。9.1.4設有電磁屏蔽室的數據中心,建筑結構應滿足屏蔽結構對荷載的要求。9.1.5電磁屏蔽室與建筑(結構)墻之間宜預留維修通道或維修口。9.1.69.2結構形式9.2.1分為自撐式和直貼式。9.2.2建筑面積小于50m2、日后需搬遷的電磁屏蔽室,結構形式宜采用可拆卸式。9.2.3電場屏蔽衰減指標大于120dB、建筑面積大于50m2的屏蔽室,結構形式宜采用自撐式。9.2.4電場屏蔽衰減指標大于60dB擇鍍鋅鋼板,鋼板的厚度應根據屏蔽性能指標確定。9.2.5電場屏蔽衰減指標大于25dB擇金屬絲網,金屬絲網的目數應根據被屏蔽信號的波長確定。9.3屏蔽件9.3.1磁屏蔽室的性能要求,安裝位置應便于檢修。9.3.2件受到限制時,可采用移動式屏蔽門。249.3.3格、供電方式和數量應根據電磁屏蔽室內設備的用電情況確定。9.3.4所有進入電磁屏蔽室的信號電纜應通過信號濾波器或進行其它屏蔽處理。9.3.5進出電磁屏蔽室的網絡線宜采用光纜或屏蔽纜線,光纜不應帶有金屬加強芯。9.3.6氣次數進行計算。9.3.7屏蔽的性能要求。2510網絡與布線系統10.1網絡系統10.1.1數據中心網絡系統應根據用戶需求和技術發展狀況進行規劃和設計。10.1.2數據中心網絡應包括互聯網絡、前端網絡、后端網絡和運管網絡。前端網絡可采用三層、二層和一層架構。10.1.3級數據中心的核心網絡設備應采用容錯系統,并應具有可擴展性,相互備用的核心網絡設備宜布置在不同的物理隔間內。10.2布線系統10.2.1數據中心布線系統設計,除應符合本規范的規定外,輔助區、支持區和行政GB50311的有關規定。10.2.2數據中心布線系統應支持數據和語音信號的傳輸。10.2.3置在一列或幾列機柜的端頭或中間位置。10.2.4承擔數據業務的主干和水平子系統應采用多模光纜、單模光纜或6A類及以上對絞電纜,傳輸介質各組成部分的等級應保持一致,并應采用冗余配置。10.2.5線箱。10.2.6主機房布線系統中12芯及以上的光纜主干或水平布線系統宜采用多芯MPO/MTP預連接系統。存儲網絡的布線系統宜采用多芯MPO/MTP預連接系統。10.2.7級數據中心宜采用智能布線管理系統對布線系統進行實時智能管理。10.2.8數據中心布線系統所有線纜的兩端、配線架和信息插座應有清晰耐磨的標簽。2610.2.9數據中心存在下列情況之一時,應采用屏蔽布線系統、光纜布線系統或采取其它相應的防護措施:1環境要求未達到本規范第5.2.2條的要求時;2網絡安全保密要求時;3安裝場地不能滿足非屏蔽布線系統與其它系統管線或設備的間距要求時。10.2.10A的要求執行。10.2.11數據中心布線系統與公用電信業務網絡互聯時,接口配線設備的端口數量和纜線的敷設路由應根據數據中心的等級,并在保證網絡出口安全的前提下確定。10.2.12纜線采用線槽或橋架敷設時,線槽或橋架的高度不宜大于150mm,線槽或橋機房天花板下方時,線槽和橋架的頂部距離天花板或其他障礙物不宜小于300mm。10.2.13主機房布線系統中的銅纜與電力電纜或配電母線槽之間的最小間距應根據機柜的容量和線纜保護方式確定,并應符合表10.2.13的規定。表10.2.13銅纜與電力電纜或配電母線槽的間距銅纜與電力電纜的敷設關系銅纜與配電母線槽的敷設關系機柜容量最小間距(kVA)()銅纜與電力電纜平行敷設-300有一方在金屬線槽或鋼管中敷銅纜與配電母線槽平行敷設150≤5設,或使用屏蔽銅纜。雙方各自在金屬線槽或鋼管中敷設,或使用屏蔽銅纜。銅纜在金屬線槽或鋼管中敷設,或使用屏蔽銅纜。80銅纜與電力電纜平行敷設-600有一方在金屬線槽或鋼管中敷銅纜與配電母線槽平行敷設300>5設,或使用屏蔽銅纜。雙方各自在金屬線槽或鋼管中銅纜在金屬線槽或鋼管中敷設,150敷設,或使用屏蔽銅纜。或使用屏蔽銅纜。2711智能化系統11.1一般規定11.1.1數據中心應設置總控中心、環境和設備監控系統、安全防范系統、火災自動GB50314GB50348、GB50116GB50464,以及本規范附錄A的要求執行。11.1.2應單獨回路配電。11.1.3應采用國際上通用的系統。11.1.4智能化系統應具備顯示、記錄、控制、報警、提示及趨勢和能耗分析功能。11.2環境和設備監控系統11.2.1環境和設備監控系統宜符合下列要求:1系統。2運行狀態應納入監控系統。3境溫度、露點溫度或相對濕度應以冷通道或以送風區域的測量參數為準。11.2.228監控的主要參數應納入設備監控系統,通信協議應滿足設備監控系統的要求。11.3安全防范系統11.3.1各系統之間應具備聯動控制功能。級數據中心主機房的視頻監控應無盲區。11.3.2緊急情況時,出入口控制系統應能接受相關系統的聯動控制信號,自動打開疏散通道上的門禁系統。11.3.3室外安裝的安全防范系統設備應采取防雷電保護措施,電源線、信號線應采用屏蔽電纜,避雷裝置和電纜屏蔽層應接地,且接地電阻不應大于10。11.3.4安全防范系統宜采用數字式系統,支持遠程監視功能。11.4總控中心11.4.1公及管理信息等信號。11.4.2監控系統、燈光控制系統、操作控制臺和座席等。2912給水排水12.1一般規定12.1.1給水排水系統應根據數據中心的等級,按本規范附錄A的要求執行。12.1.2數據中心內安裝有自動噴水滅火設施、空調機和加濕器的房間,地面應設置擋水和排水設施。12.1.3道不應布置在電子信息設備的上方。進入主機房的給水管應加裝閥門。12.1.4當地應急水車抵達現場的時間。當不能確定應急水車抵達現場的時間時,A級數據中心可按小時儲水。12.2管道敷設12.2.1數據中心內的給水排水管道應采取防滲漏和防結露措施。12.2.2穿過主機房的給水排水管道應暗敷或采取防漏保護的套管。管道穿過主機房墻壁和樓板處應設置套管,管道與套管之間應采取密封措施。12.2.3主機房和輔助區設有地漏時,應采用潔凈室專用地漏或自閉式地漏,地漏下應加設水封裝置,并應采取防止水封損壞和反溢措施。12.2.4數據中心內的給排水管道及其保溫材料應采用不低于B13013消防與安全13.1一般規定13.1.1數據中心防火和滅火系統設計,除應符合本規范的規定外,尚應符合現行國家標準《建筑設計防火規范》GB50370霧滅火系統技術規范》GB50898GB50084規范附錄A的要求執行。13.1.2級數據中心的主機房宜設置氣體滅火系統,也可設置細水霧滅火系統。當A級數據中心內的電子信息系統在其他數據中心內安裝有承擔相同功能的備份系統時,也可設置自動噴水滅火系統。13.1.3級和級數據中心的主機房宜設置氣體滅火系統,也可設置細水霧滅火系統或自動噴水滅火系統。13.1.4總控中心等長期有人工作的區域應設置自動噴水滅火系統。13.1.5數據中心應設置火災自動報警系統,并應符合現行國家標準《火災自動報警系統設計規范》GB50116的有關規定。13.1.6數據中心應設置室內消火栓系統和建筑滅火器,室內消火栓系統宜配置消防軟管卷盤。13.2防火與疏散13.2.1數據中心的耐火等級不應低于二級。13.2.2當數據中心按照廠房進行設計時,數據中心的火災危險性分類應為丙類,數據中心內任一點到最近安全出口的直線距離不應大于表13.2.2距離可增加。表13.2.2數據中心內任一點到最近安全出口的直線距離(m)地下室

單層多層高層

半地下室8060403013.2.331的直線距離不應大于表13.2.3-1門的直線距離不應大于表13.2.3-2動噴水滅火系統的區域,安全疏散距離可增加。表13.2.3-1直通疏散走道的房間疏散門至最近安全出口的直線距離()疏散門的位置單層、多層高層位于兩個安全出口之間的疏散門4040位于袋形走道兩側或盡端的疏散門2220表13.2.3-2房間內任一點至房間直通疏散走道的疏散門的直線距離()單層、多層高層222013.2.4耐火極限不低于2.0h的防火隔墻和1.5h的樓板隔開,隔墻上開門應采用甲級防火門。13.2.5建筑面積大于120m2的主機房,疏散門不應少于兩個,且應分散布置。建筑面積不大于120m2200m2機房內任一點至疏散門的直線距離不大于,可設置一個疏散門,疏散門的凈寬度不小于1.4m況下均能從機房內開啟。走廊、樓梯間應暢通,并應有明顯的疏散指示標志。13.2.6主機房的頂棚、壁板(包括夾芯材料)和隔斷應為不燃燒體,且不得采用有機復合材料。地面及其他裝修應采用不低于級的裝修材料。13.2.7當單罐柴油容量不大于50m3,總柴油儲量不大于200m3時,直埋地下的臥式柴油儲罐與建筑物和園區道路之間的最小防火間距除應符合表13.2.7符合現行國家標準《建筑設計防火規范》、《汽車加油加氣站設計與施工規范》GB50156和《石油化工企業設計防火規范》的有關規定。表13.2.7直埋地下的柴油臥式儲罐與建筑物和園區道路之間的最小防火間距32防火間距(m)從儲油罐邊沿到柴油種類及儲建筑物園區道路邊沿量一、二級主要次要三級四級

高層民高層裙房及其

道路道路用建筑廠房他建筑閃點≥℃201367.510331≤<閃點≥℃25137.51012.53350V200閃點≥℃201367.510335≤≤13.3消防設施13.3.1采用管網式氣體滅火系統或細水霧滅火系統的主機房,應同時設置兩組獨立的火災探測器,且火災報警系統應與滅火系統和視頻監控系統聯動。13.3.2制關閉房間內的風門、風閥,并應停止空調機、排風機,切斷非消防電源等。13.3.3置防止誤操作。13.3.4當數據中心與其它功能用房合建時,數據中心內的自動噴水滅火系統,應設置單獨的報警閥組。13.3.5數據中心內,建筑滅火器的設置應符合現行國家標準《建筑滅火器配置設計規范》的有關規定。滅火劑不應對電子信息設備造成污漬損害。13.4安全措施13.4.1凡設置氣體滅火系統的主機房,應配置專用空氣呼吸器或氧氣呼吸器。13.4.2數據中心應采取防鼠害和防蟲害措施。33附錄1各級數據中心技術要求技術要求項目備注A級B級C級選址包括自用和外部停車距離停車場不應小于不宜小于場距離鐵路或高速不包括各場所自身使

不應小于800米不宜小于100米公路的距離用的數據中心不包括地鐵公司自身

距離地鐵的距離不宜小于100m不宜小于80m

使用的數據中心在飛機航道范圍不包括機場自身使用內建設數據中心不宜小于8000m不宜小于1600m-的數據中心

距離飛機場距離甲、乙類廠不包括甲、乙類廠房房和倉庫、垃圾不應小于2000m-和倉庫自身使用的數填埋場據中心不包括火藥炸藥庫自

距離火藥炸藥庫不應小于3000m-

身使用的數據中心距離核電站的危不包括核電站自身使

不應小于40000m險區域用的數據中心距離住宅不宜小于100m-有可能發生洪水不宜設置數據

不應設置數據中心的區域中心地震斷層附近或不宜設置數據

不應設置數據中心有滑坡危險區域中心從火車站、飛機不應少于條道路---場到達數據中心的交通道路環境要求冷通道或機柜進風區域的溫度18C~27C冷通道或機柜進風區域的相對濕露點溫度5.5C~15,同時相對濕度不大于不得結露度和露點溫度主機房環境溫度和相對濕度5C~45℃,,同時露點溫度不大于27C(停機時)34主機房和輔助區使用磁帶驅動時<5/h,溫度變化率使用磁盤驅動時<℃輔助區溫度、相18C~28、35%~75%輔助區溫度、相5C~35C20%~80%不間斷電源系統電池室溫度20C~30C每立方米空氣中大于主機房空氣粒子濃度應少于17,600,000或等于0.5的懸浮粒子數建筑與結構抗震設防分類不應低于乙類不應低于丙類不宜低于丙類-組合值系數Ψ主機房活荷載標根據機柜的擺放密度

8~頻遇值系數Ψ準值(kN/m2)確定荷載值準永久值系數Ψq=0.8主機房吊掛荷載

1.2(kN/m2)不間斷電源系統室活荷載標準值8~(kN/m2)電池室活荷載標16蓄電池組4層擺放

準值(kN/m2)總控中心活荷載

6標準值(kN/m2)鋼瓶間活荷載標

8準值(kN/m2)電磁屏蔽室活荷載標準值8~(kN/m2)主機房外墻設采

不宜光窗防靜電活動地板不宜小于500mm作為空調靜壓箱時的高度防靜電活動地板僅作為電纜布線使用

不宜小于250mm的高度時屋面的防水等級ⅠⅠⅡ35空氣調節主機房和輔助區設置空氣調節系應宜-統不間斷電源系統電池室設置空調宜可-降溫系統主機房保持正壓應可-冷凍機組、冷凍N+XN+1N-(X=1N)冷卻塔冷凍水供水溫度7C~21C冷凍水回水溫度12C~27C機房專用空調N+XN+1N-(X=1N)主機房中每個區域主機房中每個區域冗余一臺冗余X臺采用不間斷電源空調末端風機、控控制系統--系統供電的設備制系統、末端冷凍水泵蓄冷裝置供應冷不應小于不間斷電--凍水的時間源設備的供電時間雙冷源可--冷凍水供回水管雙供雙回、環形布單一路徑-網置冷卻水補水儲存需要-裝置冷熱通道隔離需要-電氣技術供電電源應由雙重電源供電宜由雙重電源供電兩回線路供電-供電網絡中獨立于正常電源的專可作為備用電源---用饋電線路A級也可采用其他避變壓器2NN+1N免單點故障的系統配置后備柴油發電機(N+X~N+1不間斷電源系統-36系統N)當供電電源只有一的供電時間滿足路時需設置后備柴信息存儲要求時,油發電機系統可不設置柴油發電機。后備柴油發電機應包括不間斷電源系統的基本容量、空調

--的基本容量和制冷設備的基本容量。1保障時,燃料存儲量柴油發電機燃料僅需大于外部供油時

滿足--存儲量間。2滋生。2N或()N+1NN≤4(M=234??)不間斷電源系統一路()UPS和配置--滿足3.2.2條要求時一路市電供電可以,也可以--滿足3.2.3條要求時

(N+1)不間斷電源系統需要--自動轉換旁路不間斷電源系統需要--手動維修旁路不間斷電源系統15min7min根據實際需要確電池最少備用時柴油發電機作為后柴油發電機作為后-定間備電源時備電源時雙路電源(其中至少一路為應急電雙路電源,末端切

采用放射式配電空調系統配電源),末端切換。換。采用放射式配-系統采用放射式配電系電系統。統。容錯配置的變配電變配電所物理隔設備應分別布置在離不同的物理隔間內。電子信息設備交流供電電源質量要求穩態電壓偏移范+~-10交流供電時

圍(%)37穩態頻率偏移范±交流供電時

圍()輸入電壓波形失電子信息設備正常工≤5真度()作時允許斷電持續時不同電源之間進行切0~間()換時網絡與布線系統OM3/OM4多模光纜、OM3/OM4多模光纜、

承擔數據業務的單模光纜或類以

單模光纜或類以主干和水平子系上對絞電纜,主干--上對絞電纜,主干統和水平子系統均應子系統應冗余。

冗余。進線間不少于個不少于個1個智能布線管理系宜可--統配電電纜宜采用線纜線纜標識系統應在線纜兩端打上標簽

標識系統應采用級或低在隱蔽通風空間煙無鹵阻燃電纜,也可采用同等級的其

敷設的通信纜線--OFNP或它電纜或光纜防火要求

纜。公用電信配線網2個以上2個1個-絡接口環境和設備監控系統空氣質量粒子濃度離線定期檢測空氣質量溫度、露點、壓差溫度、露點漏水檢測報警裝設漏水感應器強制排水設備設備的運行狀態集中空調和新風設備運行狀態、濾網壓差系統、動力系統在線檢測或通過數據狀態參數:接口將參數接入機房開關、制冷、加熱、加濕、除濕、水閥開度、水流量環境和設備監控系統機房專用空調報警參數:中溫度、相對濕度、傳感器故障、壓縮機壓力、加濕器水位、風量供配電系統開關狀態、電流、電壓、有功功率、功率因數、諧波含量、電子信息設備用電量、根據需要選擇38數據中心用電量、電能利用效率輸入和輸出功率、電壓、頻率、電流、功率因數、負荷率;電池輸入電壓、電流、不間斷電源系統容量;同步不同步狀態、不間斷電源系根據需要選擇統系統故障。監控每一個蓄電池監控每一組蓄電池電池的電壓、內阻、故的電壓、故障和環-障和環境溫度境溫度柴油發電機系統-

頻率、電壓、功率因數主機集中控制和采用帶外管理或KVM切換系統--管理安全防范系統發電機房、變配出入控制(識讀設電室、電池室、備采用讀卡器)、入侵探測器機械鎖-動力站房視頻監視推桿鎖、視頻監視安全出口推桿鎖-

總控中心連鎖報警出入控制(識讀設備采用讀卡器)、視頻總控中心機械鎖-監視出入控制安防設備間(識讀設備采用讀入侵探測器機械鎖卡器)出入控制(識讀設出入控制(識讀設

備采用讀卡器)或機械鎖

主機房出入口備采用讀卡器)、-

人體生物特征識入侵探測器

視頻監視別、視頻監視主機房內視頻監視--建筑物周圍和停適用于獨立建筑的機

視頻監視-車場房給水排水1保障時,水存儲量僅冷卻水儲水量滿足12h--需大于外部供水時間。239用要求。與主機房無關的給排水管道穿越不應不宜-主機房主機房地面設置用于冷凝水排水、空排水系統應調加濕器排水、消防噴灑排水、管道漏水消防與安全主機房設置氣體宜-滅火系統變配電、不間斷電源系統和電池宜-

室設置氣體滅火系統主機房設置細水可-

霧滅火系統變配電、不間斷電源系統和電池可-

室設置細水霧滅火系統主機房設置自動可噴水滅火系統(當兩個或兩個以

可-

上數據中心互為備份時)吸氣式煙霧探測作為早期報警,靈敏火災報警系統宜-度嚴于%/m40本規范用詞說明1為便于在執行本規范條文時區別對待,對要求嚴格程度不同的用詞說明如下:1)表示很嚴格,非這樣做不可的用詞:正面詞采用”,反面詞采用“。2)表示嚴格,在正常情況下均應這樣做的用詞:正面詞采用應,反面詞采用“”“。3)表示允許稍有選擇,在條件許可時首先應這樣做的用詞:正面詞采用宜,反面詞采用“”;表示有選擇,在一定條件下可以這樣做的用詞,采用”。2本規范中指明應按其他有關標準、規范執行的寫法為應符合??的規定”“應按??執行。41引用標準目錄《建筑設計防火規范》GB50016《建筑抗震鑒定標準》GB50023《建筑照明設計標準》GB50034《供配電系統設計規范》GB50052《建筑物防雷設計規范》GB50057《自動噴水滅火系統設計規范》GB50084《工業企業噪聲控制設計規范》GB/T50087《火災自動報警系統設計規范》GB50116《建筑滅火器配置設計規范》GB50140《汽車加油加氣站設計與施工規范》GB50156《石油化工企業設計防火規范》GB50160《公共建筑節能設計標準》GB50189《建筑內部裝修設計防火規范》GB50222《綜合布線系統工程設計規范》GB50311《智能建筑設計標準》GB50314《建筑物電子信息系統防雷技術規范》GB50343《安全防范工程技術規范》GB50348《混凝土加固結構規范》GB50367《氣體滅火系統設計規范》GB50370《視頻顯示系統工程技術規范》GB50464《電子工程防靜電設計規范》GB50611《民用建筑供暖通風與空氣調節設計規范》GB50736《細水霧滅火系統技術規范》GB50898《建筑

溫馨提示

  • 1. 本站所有資源如無特殊說明,都需要本地電腦安裝OFFICE2007和PDF閱讀器。圖紙軟件為CAD,CAXA,PROE,UG,SolidWorks等.壓縮文件請下載最新的WinRAR軟件解壓。
  • 2. 本站的文檔不包含任何第三方提供的附件圖紙等,如果需要附件,請聯系上傳者。文件的所有權益歸上傳用戶所有。
  • 3. 本站RAR壓縮包中若帶圖紙,網頁內容里面會有圖紙預覽,若沒有圖紙預覽就沒有圖紙。
  • 4. 未經權益所有人同意不得將文件中的內容挪作商業或盈利用途。
  • 5. 人人文庫網僅提供信息存儲空間,僅對用戶上傳內容的表現方式做保護處理,對用戶上傳分享的文檔內容本身不做任何修改或編輯,并不能對任何下載內容負責。
  • 6. 下載文件中如有侵權或不適當內容,請與我們聯系,我們立即糾正。
  • 7. 本站不保證下載資源的準確性、安全性和完整性, 同時也不承擔用戶因使用這些下載資源對自己和他人造成任何形式的傷害或損失。

評論

0/150

提交評論